JJM® Neutralizer ReFill Kit, 150 MBH BTU, 0.5 - 1.2 gal/hr, 1 - 1/2 in NPT Input/Output Connection, Horizontal Mounting, Solid PVC, 10-1/2 in L x 2-3/4 in Dia
BTU Rating |
: |
150 MBH |
Connection Type |
: |
1 - 1/2 in NPT Input/Output |
Dimensions |
: |
10-1/2 in L x 2-3/4 in Dia |
Flow Rate |
: |
0.5 - 1.2 gal/hr |
Material |
: |
Solid PVC |
Mounting Type |
: |
Horizontal |
- The contractor shall supply and install fireside condensate neutralizing tubes for each boiler condensate drain and all flue pipe condensate drains
- The condensate tubes shall be designed to raise the PH level 10 - 30 times more towards the neutral point of the PH being discharged by the boiler or furnace
- The installing contractor shall supply all boilers/furnaces and vent condensate drains with "P-traps" and unions before the neutralizing tubes
- All piping shall be PVC and supplied/installed by the contractor, plastic tubing is an acceptable alternative when used with barbed fittings and hose clamps, all PVC joints shall be glued in place and all barbed fittings shall be secured with tie wraps
- The boiler and flue condensate drains shall not be combined into one-neutralizer
- The contractor shall inform the owner of any maintenance or scheduled recharge of the tube's limestone aggregate as described in the manufacturer's installation and owner manual
-