LAARS® Neotherm NTH NTH750NJX3 Gas Fired Water Boiler, 96.6% Thermal and Combustion AFUE, 120 VAC, 1 -Phase

  • Manufacturer: Bradford White Corporation
  • Brand Name: LAARS®
  • Part Number: ERP_016739
  • MPN: NTH750NJX3
  • Min. Order Qty: 1
  • Qty. Interval: 1
  • Sign In for Availability

LAARS® Neotherm Gas Fired Water Boiler, Series: NTH, NTH-750 Model, 120 VAC, 219.8 kW Input, 212.1 kW Output, 1 -Phase, 96.6% Thermal and Combustion AFUE, 750000 Btu/hr Input, 723000 Output BTU, 2 in NPT Water, 1-1/2 in NPT Gas Connection, Natural Gas Fuel, Direct Exhaust Vent, 100 ft Equivalent Vent L, 6 in Vent Dia Chimney/Breeching/Vent Size, Spark Ignition, Stainless Steel, 24-1/2 in W x 51 in H x 42-3/4 in D

AFUE Rating      :      96.6% Thermal and Combustion
BTU Rating      :      750000 Btu/hr Input, 723000 Output
Chimney/Breeching/Vent Size      :      100 ft Equivalent Vent L, 6 in Vent Dia
Connection Type      :      2 in NPT Water, 1-1/2 in NPT Gas
Dimensions      :      24-1/2 in W x 51 in H x 42-3/4 in D
Fuel Type      :      Natural Gas
Ignition Type      :      Spark
Material      :      Stainless Steel
Model      :      NTH-750
Phase      :      1
Power Rating      :      219.8 kW Input, 212.1 kW Output
Vent Type      :      Direct Exhaust
Voltage Rating      :      120 VAC
  • Stainless steel heat exchanger with welded construction (no gaskets)
  • Easy to service
  • Low NOx system (10 mg/L) exceeds the most stringent regulations for air quality
  • Laars integrated control system
  • Integrates with building automation systems
  • Modulation down to 20% of full fire 5:1 turndown
  • Sealed combustion chamber, pre-mix stainless steel burner
  • Horizontal or vertical direct vent and air terminals
  • Vent temperature cut-off feature
  • 160 lb/sq-in maximum working pressure
  • 75 lb/sq-in ASME rated pressure relief valve
  • Multiple pump control for boiler pump, system pump and indirect domestic water pump, each with delay
  • Outdoor reset with customizable reset curves, domestic hot water override and warm weather shutdown
  • Outdoor air temperature sensor
  • Indirect water heater priority
  • Sensor for indirect domestic water tank
  • Temperature and pressure gauge, drain valve
  • Electronic PID modulating control stages upto 8-boilers
  • Large color touch screen, alarm output
  • Accepts external 4 - 20 mA modulation signal